Published · Updated · 11 min read
By Camas Bath
The short answer
A shower resists failure when it meets six testable standards: a membrane certified to ANSI A118.10, an ANSI A108 installation method, a code-compliant pre-slope built before waterproofing, correctly detailed backer board, vapor-conscious mortar selection, and a flood test before tile (TCNA). In Clark County’s wet marine climate, tile and grout are the finish — never the barrier itself.
Key facts
- The current edition of ANSI A118.10, the standard for load-bearing, bonded, waterproof membranes under tile, is 2023; crack-isolation standard A118.12 is the 2014 edition, reaffirmed in 2024 (TCNA ANSI standards).
- To meet ANSI A118.10, a membrane must show no visible water penetration after 48 hours, a shear bond to tile of at least 50 psi and a breaking strength of at least 170 psi (TEC Water Defense Pro data sheet).
- Schluter calls a 24-hour flood test typical and recommends waiting at least 24 hours after setting KERDI before starting it, longer around 50–60°F (Schluter).
- LATICRETE HYDRO BAN can be flood tested 2 hours after it turns dark olive green at 70°F and 50% RH; in cooler or drier conditions the wait is 24 hours after the color change (LATICRETE).
- Washington enforces the 2021 Uniform Plumbing Code, effective March 15, 2024, which sets the shower-pan slope and liner rules a waterproofed shower is inspected against (WA State Building Code Council).
Key takeaways
- Tile and grout are water-permeable finish materials, per the TCNA Handbook — the waterproofing is a membrane installed behind and beneath them, not the tile itself.
- A real waterproofing membrane is tested to ANSI A118.10 (current edition 2023): no water penetration under a 24-inch water column for 48 hours, and at least 50 psi shear bond to tile; "water-resistant" is a different, lower bar.
- Slope has to exist before the membrane goes down. Washington's adopted plumbing code (the 2021 UPC) requires a finished shower-floor slope of 1/8 to 1/2 inch per foot toward the drain, and TCNA installation methods put standard field practice at 1/4 inch per foot.
- Bonded (sheet or liquid) membrane systems and traditional mortar-bed-and-liner systems can both meet code when installed to a recognized ANSI A108 method — they fail differently, not equally.
- Backer board is a substrate, not a waterproofing layer. Building Science Corporation and the DOE-backed Building America Solution Center both note cement board must be coated or backed with its own water-resistive barrier.
- A flood test — filling the pan and holding water before a single tile is set — is the only standards-based way to confirm a shower actually holds water. Schluter calls 24 hours typical, after the membrane has cured.
1. Start with the principle: tile is the finish, not the barrier
The TCNA Handbook for Ceramic, Glass, and Stone Tile Installation — the reference tile setters and inspectors actually use — treats tile and grout as porous finish materials, not a water barrier. Both let some water through by design. The layer that is actually engineered to stop water from reaching your framing is a membrane installed behind and beneath the tile, sealed at every seam, corner, and pipe penetration, before a single tile goes up.
That's the frame for everything below. None of these six standards are about how the finished shower looks — they're about the hidden assembly a homeowner never sees again once the grout goes in. For a full breakdown of the three membrane systems pros actually use, see our companion shower waterproofing guide.
The line worth remembering
A flawless tile job over skipped or under-built waterproofing still fails. It just takes longer to show — and in a wet climate, it shows faster than you'd think.
2. Standard 1 — a membrane actually rated to ANSI A118.10
Not every product marketed as "waterproofing" has been tested the same way. ANSI A118.10 (sometimes written "ANSI 118.10") — American National Standard Specifications for Load Bearing, Bonded, Waterproof Membranes for Thin-Set Ceramic Tile and Dimension Stone Installation — is the specific standard that defines what a membrane has to survive to be called load-bearing, bonded, and waterproof, not merely water-resistant. It applies to trowel-applied liquid membranes and sheet membranes alike, and it's maintained and referenced by TCNA's ANSI standards program.
In practice, this is the single fastest thing to ask a contractor or check a product data sheet for: does the membrane meet ANSI A118.10? If the answer is a generic "yes it's waterproof" without the standard number, that's worth pressing on before tile goes up over it.
The current edition is ANSI A118.10-2023, though test reports still commonly cite the 2014 edition (reaffirmed 2019) — an IAPMO test report on Laticrete Hydro Ban issued in September 2025 tested to A118.10-2014 [R2019]. Either way, the standard sets measurable minimums. The waterproofness test is a hydrostatic one: the membrane is held under a 24-inch column of water for 48 hours per ASTM D4068 Annex 2 and must show no visible water penetration. The remaining tests cover how well it bonds to tile, how strong it is, and whether it stays stable and mold-free.
| Test | A118.10 requirement | Method |
|---|---|---|
| Waterproofness | No visible water penetration after 48 hours (24-inch water column) | ASTM D4068, Annex 2 |
| Shear bond strength to tile | 50 psi minimum at 7 days, 7 days water-immersed, 4 weeks, 12 weeks, and 100 days water-immersed | ASTM C482 |
| Breaking strength | 170 psi minimum | ASTM D751 |
| Seam strength | 8 lb per inch of width | A118.10 |
| Dimensional stability | Maximum 0.7% length change (tested at +158°F and −15°F) | ASTM D1204 |
| Fungus and micro-organism resistance | Shall not support mold growth | A118.10 |
Sources: TEC Water Defense Pro product data sheet (H.B. Fuller, September 2025), which prints the A118.10 requirement column; IAPMO test report 2212-25024 (Laticrete Hydro Ban, 2025) for test methods and conditions. Edition: TCNA ANSI standards list.
Standard 1, continued — how does A118.10 differ from A118.12, and what does the plumbing code accept?
ANSI A118.12 is a different standard: Specifications for Crack Isolation Membranes. Where A118.10 tests waterproofing and bond, A118.12 tests movement — a point-load test of at least 1,000 lb without cracking tile, and shear-deflection and crack-resistance tests at a standard (1/16 inch) or high-performance (1/8 inch) level. Many membranes are tested to both; a product rated only to A118.12 is not, on that basis alone, a waterproofing membrane.
On the code side, the 2021 Uniform Plumbing Code that Washington enforces does not name A118.10 in its shower-liner section. UPC 408.7 lists sheet plastic (PVC to ASTM D4551 or CPE to ASTM D4068), lead, copper, hot-mopped felt, or “other durable and watertight materials.” A bonded membrane used as the shower pan qualifies as one of those other materials with the building official’s approval, which in practice rests on the product being listed as a shower pan liner — IAPMO lists liquid membranes in that category against A118.10. Laticrete’s own data sheet tells installers to obtain approval from the local building code authority before using its membrane in shower pan applications.
The practical check
Ask for two things on the data sheet: ANSI A118.10 compliance, and a shower pan liner listing (for example IAPMO). The first tells you how the membrane performs; the second is what lets an inspector accept it as the shower pan.
3. Standard 2 — slope built before the membrane, not corrected after
Washington has adopted the 2021 Uniform Plumbing Code, per the WA State Building Code Council, which requires shower floors to slope toward the drain at 1/8 to 1/2 inch per foot (UPC 408.5). TCNA installation methods put standard field practice at 1/4 inch of pitch per foot — enough to clear standing water without creating an unsafe walking surface.
The critical detail is sequencing: on a bonded system, that slope is built into a pre-sloped substrate (foam shower base or mortar pre-slope) before the waterproof membrane goes on top of it. Grout lines and tile thickness cannot fix a flat or reverse-pitched substrate underneath — they just hide it until water starts pooling against a threshold or curb. This is especially true on curbless and low-threshold layouts, where a linear drain has to pull the entire pan to a single, precise plane; see our walk-in showers page for how that's planned locally.

4. Standard 3 — a recognized ANSI A108 method, bonded or traditional
Both approaches can meet code and last decades. What separates them isn't the category — it's whether the specific method was followed to spec. A bonded system fails when the membrane is under-applied or a seam isn't sealed; a traditional system fails when the pre-slope is flat, the liner is punctured, or weep holes clog. Correct membrane installation also sets up everything that comes after it, from grout selection to how well custom tile and stonework bonds and stays crack-free. See our best shower wall materials guide for how the wall assembly above the pan factors into the same decision.
- ANSI A108 is a family of American National Standard specifications — maintained by TCNA — that define how ceramic and stone tile assemblies actually get installed, method by method, over different substrates and membrane types.
- Bonded (sheet or liquid) membrane systems: a sheet or liquid membrane certified to ANSI A118.10 is applied directly over backer board or a pre-sloped foam base, installed to its corresponding ANSI A108 method, then tiled directly over it in thin-set.
- Traditional mortar-bed systems: a pre-slope mortar bed, then a PVC or CPE liner — CPE liner material is specified under ASTM D4068 for tensile strength, puncture resistance, and hydrostatic pressure resistance — then a second mortar bed on top, draining through a clamping drain with weep holes.
5. Standard 4 — backer board is a substrate, not a waterproofing layer
This is the standard most often skipped by assumption. Building Science Corporation's Info-407: Air Barriers — Tub, Shower and Fireplace Enclosures is explicit: cement board is not waterproof on its own — it has to be coated with a fluid-applied waterproofing or backed by its own water-resistive barrier that drains. The DOE-backed Building America Solution Center reaches the same conclusion and adds that moisture-resistant gypsum board ("green board") is not recommended behind a shower at all.
In other words: cement board, fiber-cement board, or a bonded foam substrate are the right starting materials, but none of them are a finished waterproofing system by themselves. The membrane standard from item 2 above still has to go over them.
6. Standard 5 — vapor-conscious detailing, especially here
A detail installers sometimes get backward: once a continuous waterproof membrane is in place, the assembly behind it can no longer dry by evaporation in either direction. Building Science Corporation's BSI-113: Stoned explains why this matters for the mortar itself — polymer-modified thin-set needs evaporation to fully cure and cross-link. Trapped behind a vapor-blocking membrane with no path to dry, a modified thin-set can fail to bond correctly, and sustained alkalinity can break down the polymer over time. The standard response is straightforward: use unmodified thin-set directly against a bonded waterproof membrane, per the membrane manufacturer's installation instructions.
It's a small material choice with an outsized consequence, and it's exactly the kind of detail that's invisible once the tile is up.
7. Standard 6 — verify with a flood test before tile goes up
Every standard above is a design requirement. The flood test is the verification step: after the membrane is installed and before any tile is set, the drain is dammed, the pan is filled with water, and it's left to sit — confirming the assembly holds water and then drains completely once the dam is released. It's the one point in the process where a hidden failure can still be caught and fixed cheaply, instead of discovered years later as a soft subfloor or a moldy ceiling below.
If a contractor skips this step or can't describe how they verify a pan before tiling, that's worth asking about directly.

How do you flood test a shower, and how long should it last?
Schluter describes the procedure plainly: stop the waste line with a test plug, fill the base of the shower with water, mark the water level, and leave it for a specified time — 24 hours is typical. If there are no leaks, the shower passes. Check the plug first by filling just the drain and pipe; if the plug holds, keep filling the pan. On a curbless or barrier-free shower there is no curb to hold the water, so Schluter calls for a temporary dam at the threshold, such as a 2x4 sealed with silicone.
Pass or fail comes down to two observations: the marked water level has not dropped beyond what evaporation explains, and nothing has appeared below or beside the shower — no damp subfloor, no wet framing, no stain on a ceiling underneath. A drop with no visible leak still means finding the cause before tile goes on; start with the drain connection, seams, corners and pipe penetrations — the joints the membrane has to be sealed at.
The test can only start once the membrane is cured, and the wait depends on the product. Two examples from manufacturer literature:
| Membrane | Wait before flood testing | Condition that changes it |
|---|---|---|
| Schluter KERDI (sheet, set in thin-set) | At least 24 hours after setting KERDI, so the thin-set reaches final set at the seams | Wait longer if temperatures are much lower, around 50–60°F |
| LATICRETE HYDRO BAN (liquid) | 2 hours after the color turns from sage green to dark olive green | Below 70°F and 50% RH: wait 24 hours after the color change |
Sources: Schluter FAQ, “What is a water test?”; LATICRETE HYDRO BAN sell sheet DS-10081. Always follow the data sheet for the exact product on the job — cure times differ even between products from the same maker.
Cold-season timing in Clark County
Both manufacturers lengthen the wait in cool conditions. In an unheated bathroom during a Clark County winter, a membrane may need the longer cure before it can be flood tested — worth building into the schedule rather than skipping the test to keep tile on track. On a Camas Bath walk-in shower in Vancouver or Camas, the pan is sloped and flood-tested before any tile is set.
Why does shower waterproofing matter more in a marine climate?
None of these standards change because of geography — but the cost of skipping one does. Clark County sits in a marine west coast climate with elevated indoor humidity for a large share of the year, which gives hidden leaks a long wet season — fall through spring — with little chance to dry out. A membrane that's slightly under-applied, a pre-slope that's slightly flat, or a seam that's slightly unsealed tends to turn into rot and mold on a shorter timeline here than in a drier climate. Our guide to bathroom materials for the PNW climate covers the broader material picture beyond the shower itself.
Washington also requires anyone performing construction work for pay — including tile and waterproofing subcontractors — to hold active contractor registration with the Department of Labor & Industries (L&I), which includes bonding and insurance minimums. Ask for the L&I registration number on any shower project and verify it before signing a contract. If you're planning ahead, check permit requirements for a Camas bathroom remodel as well, since most full shower rebuilds require one.
What to ask before you hire
Does the membrane meet ANSI A118.10? What ANSI A108 method is being used? Is the pre-slope built before or after the membrane? Is the thin-set against the membrane unmodified? Will there be a flood test before tile goes up? A contractor who answers all five without hesitation is working to the actual standards.
Ready to plan your Clark County bathroom?
1-year workmanship warranty · Free in-home consultation
Frequently asked questions
- Is tile itself waterproof?
- No. Tile and grout are water-permeable finish materials — water passes through both. Per the TCNA Handbook, the actual barrier is a membrane installed behind and beneath the tile, across the pan, walls, seams, and penetrations. The tile is what you see; the membrane is what keeps water out of the framing.
- What is ANSI A118.10?
- ANSI A118.10 is the American National Standard that defines the test methods and minimum requirements for load-bearing, bonded, waterproof membranes used under thin-set ceramic tile and stone. It applies to both sheet and liquid-applied membranes and is maintained by TCNA. A membrane that meets it has been tested to a specific waterproofing standard, not just marketed as water-resistant.
- What tests does ANSI A118.10 require?
- ANSI A118.10 requires tests for waterproofness (no visible water penetration after 48 hours under a 24-inch water column, per ASTM D4068), shear bond strength to tile of at least 50 psi at several ages including after water immersion, breaking strength of at least 170 psi, seam strength of 8 lb per inch, dimensional stability within 0.7%, and resistance to mold growth.
- What is the difference between ANSI A118.10 and A118.12?
- ANSI A118.10 covers load-bearing, bonded waterproof membranes; A118.12 covers crack isolation membranes, tested for point load, shear deflection and crack resistance. A membrane rated only to A118.12 is not, on that basis, a waterproofing membrane.
- Are bonded membrane showers better than traditional mortar-bed showers?
- Neither system is inherently disqualified — both can pass inspection and last decades when installed to a recognized ANSI A108 method. A bonded (sheet or liquid) membrane system typically fails from an under-applied membrane or unsealed seam; a traditional mortar-bed-and-liner system typically fails from a flat pre-slope, a punctured liner, or clogged weep holes. The installer's adherence to the specific method matters more than which category is chosen.
- What slope does a shower floor need in Washington?
- Washington enforces the 2021 Uniform Plumbing Code, which requires the finished shower floor to slope toward the drain at 1/8 to 1/2 inch per foot, with the liner under a mortar bed sloped 1/4 inch per foot to the weep holes. TCNA installation methods put standard field practice at 1/4 inch per foot.
- How long should a shower flood test last?
- Schluter calls 24 hours typical: plug the drain, fill the pan, mark the water level and check it the next day. The test can only begin after the membrane cures — at least 24 hours after setting Schluter KERDI, or 2 hours after LATICRETE HYDRO BAN changes color at 70°F and 50% RH (24 hours if cooler). Follow the data sheet for your product.
- What counts as a pass or fail on a shower flood test?
- A pass means the marked water level holds, allowing only for evaporation, and no water shows up below or beside the shower. A dropping level or any damp subfloor, framing or ceiling below is a fail: find and repair the leak — check the drain connection, seams, corners and pipe penetrations first — then retest before any tile is set.
- How do you flood test a curbless shower?
- To flood test a curbless shower, build a temporary dam across the threshold so the pan can hold water — Schluter suggests a 2x4 sealed with silicone — then plug the drain, fill, mark the level and wait, as for any shower. Remove the dam after the shower passes.
- Do I need a licensed contractor for shower waterproofing in Clark County?
- Yes. Washington law requires anyone performing construction work for pay, including tile and waterproofing subcontractors, to hold active contractor registration with the Department of Labor & Industries (L&I), which carries bonding and insurance minimums. Ask for the L&I registration number and verify it's active before signing a contract.
Sources
- Schluter — What is a water test? How do I perform one on the Schluter-Shower System? (manufacturer FAQ)
- LATICRETE — HYDRO BAN sell sheet DS-10081 (flood-test timing)
- TEC Water Defense Pro — product data sheet with ANSI A118.10 requirement column (2025)
- IAPMO test report 2212-25024 — Laticrete Hydro Ban (ANSI A118.10)
- IAPMO — 2021 Uniform Plumbing Code (408.7 shower liners)
- Tile Council of North America — TCNA Handbook for Ceramic, Glass, and Stone Tile Installation
- Tile Council of North America — ANSI Standards (A118.10, A108 family)
- ASTM International — D4068, CPE Sheeting for Concealed Water-Containment Membrane
- Building Science Corporation — BSI-113: Stoned (waterproof membranes, thin-set, and moisture)
- Building Science Corporation — Info-407: Air Barriers, Tub, Shower and Fireplace Enclosures
- Building America Solution Center (DOE / PNNL) — Walls Behind Showers and Tubs
- Washington State Building Code Council — Plumbing Code Amendments (2021 UPC)
- Washington State L&I — Contractor Registration
Claims and figures are drawn from the sources above and provided for general guidance; your project may vary. For a fixed price on your specific bathroom, request a free estimate.





