The short answer
Washington enforces the 2023 National Electrical Code through L&I (WAC 296-46B), replaced by the 2026 edition on December 31, 2026. Bathroom receptacles need GFCI protection and a 20-amp branch circuit, a receptacle must sit within 3 feet of each sink, and none may go within 3 feet of a tub or shower. In Clark County, L&I issues the permit — except inside Vancouver, which issues its own.
Electrical work is the part of a bathroom remodel that is regulated by a different agency from everything else. In most of Clark County, plumbing and building permits come from the city or county, while electrical permits and inspections come from Washington’s Department of Labor & Industries (L&I). The code is also different: Washington adopts the National Electrical Code (NEC) with its own amendments in chapter 296-46B WAC.
This guide summarizes the bathroom-specific rules. It is not a substitute for the code or for an inspector’s interpretation of a particular installation.
Key facts
- Washington adopted the 2023 National Electrical Code effective April 1, 2024, and the 2026 edition replaces it effective December 31, 2026 (WAC 296-46B-010).
- Washington requires GFCI protection for fixed electrical equipment with exposed grounded metal parts in an enclosed shower or within 5 feet of the top inside edge of a bathtub (WAC 296-46B-210).
- Under the 2023 NEC, at least one receptacle outlet must be installed within 3 feet of the outside edge of each bathroom sink (NEC 210.52(D), Mike Holt Enterprises).
- The 2023 NEC bars receptacles from a zone 3 feet horizontally and 8 feet vertically from the top of a bathtub rim or shower threshold (NEC 406.9(C), ExpertCE).
- A Washington homeowner may do electrical work on their own residence without a license, but not on property offered for sale within 12 months of acquiring it (RCW 19.28.261).
Key takeaways
- Washington enforces the 2023 NEC (WAC 296-46B); the 2026 NEC applies to permits issued on or after December 31, 2026.
- Bathroom receptacles need GFCI protection; Washington also requires GFCI for fixed equipment with exposed metal parts in an enclosed shower or within 5 feet of a tub.
- At least one 20-amp circuit serves bathroom receptacles; it may also serve lights and a fan only when it serves a single bathroom.
- A receptacle is required within 3 feet of each sink; none may be within 3 feet of a tub or shower, up to 8 feet high.
- Electrical permits come from L&I everywhere in Clark County except inside Vancouver city limits, where the city issues them.
Which code applies
WAC 296-46B-010 adopts the 2023 edition of the NEC, effective April 1, 2024. The same section says that effective December 31, 2026, the 2026 edition replaces it. Adopted standards apply based on the date the electrical permit is issued, so a project permitted before December 31, 2026 is inspected to the 2023 NEC and one permitted on or after that date to the 2026 NEC.
The rules below are from the 2023 NEC and Washington’s amendments unless noted.
Do Washington bathroom outlets need GFCI protection?
NEC 210.8(A)(1) requires ground-fault circuit-interrupter (GFCI) protection for receptacles in dwelling unit bathrooms (Mike Holt Enterprises). GFCI protection trips the circuit when current leaks to ground — the risk that wet hands and metal fixtures create.
Washington adds its own rule in WAC 296-46B-210: fixed electrical equipment with exposed grounded metal parts that is inside an enclosed shower area, or within five feet of the top inside edge of a bathtub, must have GFCI protection. That reaches beyond receptacles to hard-wired equipment near the tub or shower.
One narrow exception in the NEC: a receptacle built into a bathroom exhaust fan does not need GFCI protection unless the fan’s instructions call for it.
Does a Washington bathroom need a 20-amp circuit?
NEC 210.11(C)(3) requires at least one 120-volt, 20-amp branch circuit to supply the bathroom receptacle outlets, and that circuit is not to supply other outlets. The code allows one exception: where the 20-amp circuit supplies a single bathroom, outlets for other equipment in that same bathroom — such as lighting or a fan — may be on it, within the limits of 210.23(B) (NFPA 70-2023 errata).
In practice that gives two common layouts: one 20-amp circuit shared by the receptacles of more than one bathroom, with lights and fans elsewhere; or one 20-amp circuit per bathroom that may also carry that bathroom’s lights and fan. Equipment such as a heated floor or steam generator is circuited according to its manufacturer’s installation instructions.
Where can bathroom receptacles go, and where can they not?
Under NEC 210.52(D) (Mike Holt Enterprises), at least one receptacle outlet must be installed within 3 feet of the outside edge of each bathroom sink, and it can be no more than 12 inches below the top of the sink or countertop. A double vanity with two basins more than 6 feet apart therefore needs a receptacle near each.
NEC 406.9(C) (ExpertCE) keeps receptacles out of the tub and shower and out of a zone extending 3 feet horizontally from the outside edge of the bathtub or shower stall and from the floor to 8 feet above the tub rim. The zone does not extend through a wall, door, window or fixed barrier. In a bathroom too small to provide the full zone, the receptacle required near the sink is still permitted, and a single receptacle is permitted for an electronic toilet or personal hygiene device such as a bidet seat.
| Item | Rule | Section |
|---|---|---|
| Bathroom receptacles | GFCI protection required | NEC 210.8(A)(1) |
| Fixed equipment near shower/tub | GFCI if it has exposed grounded metal parts and is in an enclosed shower or within 5 ft of the tub | WAC 296-46B-210 |
| Receptacle circuit | At least one 20-amp circuit; may also serve that room’s other outlets only if it serves a single bathroom | NEC 210.11(C)(3) |
| Receptacle at sink | Within 3 ft of each basin; no more than 12 in. below the countertop | NEC 210.52(D) |
| No-receptacle zone | Inside tub/shower and within 3 ft horizontally, up to 8 ft above the rim | NEC 406.9(C) |
| Paddle fans | No metal parts within 3 ft horizontally / 8 ft vertically of the tub rim or shower threshold | NEC 422.18(B) |
| AFCI | Not required for bathroom outlets in dwellings | NEC 210.12(B) |
| Breakers | Overcurrent devices not permitted in bathrooms | NEC 240.24 |
Sources: WAC 296-46B; NFPA 70-2023 and errata; Mike Holt Enterprises and ExpertCE 2023 NEC summaries. Inspectors apply the code text; check with L&I or the City of Vancouver for a specific installation.
Lights and fans over the tub or shower
NEC 410.10(D) sets two rules for light fixtures at the tub and shower. Hanging fixtures — cord-connected, chain- or cord-suspended fixtures, lighting track, pendants and ceiling paddle fans with lights — may not be within a zone 3 feet horizontally and 8 feet vertically from the top of the bathtub rim or shower threshold. Fixtures within the actual outside footprint of the tub or shower, up to 8 feet high, must be marked for damp locations, or for wet locations where they are subject to shower spray (EC&M; NKBA Bathroom Planning Guidelines).
The 2023 NEC adds that ceiling fans with light kits are not permitted in the bathtub and shower zone, and 422.18(B) (ExpertCE) keeps any metal part of a ceiling-suspended paddle fan out of the same 3-foot by 8-foot zone. A bathroom exhaust fan with a light is a different product; check that it is listed for installation over a tub or shower if that is where it will go.
Do Washington bathrooms need AFCI protection?
Arc-fault (AFCI) protection is required for many rooms in a home, but bathrooms are not on the 2023 NEC’s dwelling-unit list in 210.12(B) (Mike Holt Enterprises), and Washington’s amendments do not add them. GFCI, not AFCI, is the bathroom requirement. The 2023 NEC also no longer permits overcurrent devices — breakers or a panel — in a bathroom.
Permits and who may do the work
L&I says electrical work in Washington requires a permit and inspection, and the permit must be purchased before work starts, with specific exceptions listed in WAC 296-46B-901. Permits are bought by the electrical contractor, or by the property owner who will actually do the work. Under RCW 19.28.101, electrical wiring may not be covered up until it has been inspected and approved — so the rough-in inspection happens before drywall or tile.
Running an electrical business requires an electrical contractor license under RCW 19.28.041. RCW 19.28.261 lets a homeowner do electrical work on their own residence without a license, but not on a new building intended for rent, sale or lease, or on property offered for sale within 12 months of acquiring it.
In Clark County, the City of Vancouver issues its own electrical permits and performs its own inspections inside city limits; it is on L&I’s list of cities that do. Camas, Washougal, Battle Ground, Ridgefield, La Center and unincorporated Clark County are not on that list, so L&I handles electrical permits there.
How Camas Bath handles this
Bathroom electrical work on our projects is permitted with the right agency for the address — the City of Vancouver inside Vancouver city limits, L&I elsewhere — performed by licensed electrical contractors, and inspected at rough-in before the walls are closed. We lay out the outlets, lights and fan around the tub and shower zones at design stage, alongside the plumbing.
Frequently asked questions
- Do bathroom outlets need to be GFCI in Washington?
- Yes. NEC 210.8(A)(1), adopted in Washington, requires GFCI protection for dwelling-unit bathroom receptacles. Washington also requires GFCI for fixed equipment with exposed grounded metal parts in an enclosed shower or within five feet of a bathtub.
- Does a bathroom need a 20-amp circuit?
- Yes, a bathroom needs a 20-amp circuit. The NEC, as adopted in Washington, requires at least one 20-amp, 120-volt branch circuit for bathroom receptacles. If that circuit serves only one bathroom, it may also supply other equipment in that bathroom, such as lights and a fan.
- How far does an outlet have to be from a shower or tub?
- Under NEC 406.9(C), receptacles may not be installed within 3 feet horizontally of the outside edge of a bathtub or shower stall, from the floor up to 8 feet above the rim, unless a wall, door or fixed barrier separates them.
- Do bathrooms need AFCI protection?
- No, Washington bathrooms do not need AFCI protection. Bathrooms are not on the 2023 NEC’s dwelling-unit AFCI list in 210.12(B), and Washington’s amendments do not add them. GFCI protection is the bathroom requirement.
- Who issues electrical permits in Camas and Vancouver?
- In Camas, bathroom electrical permits come from Washington L&I. Inside Vancouver city limits, the City of Vancouver issues its own electrical permits and inspections. Elsewhere in Clark County, L&I.
- Can a homeowner do their own bathroom electrical work in Washington?
- Under RCW 19.28.261, a homeowner may do electrical work on their own residence without a license, except on a new building intended for rent, sale or lease or on property offered for sale within 12 months of acquiring it. A permit and inspection are still required.
Sources
- NKBA — Bathroom Planning Guidelines (PDF), Guideline 25
- WAC 296-46B-010 — Electrical code adoption (2023 NEC; 2026 NEC effective Dec. 31, 2026)
- WAC 296-46B-210 — Washington amendments to NEC Article 210 (GFCI)
- Washington L&I — Electrical permits, fees and inspections
- Washington L&I — City electrical permits and inspections
- RCW 19.28.041 — Electrical contractor license required
- RCW 19.28.101 — Inspection before concealment
- RCW 19.28.261 — Exemptions (homeowner work)
- NFPA — NFPA 70 (2023) errata (210.11(C)(3) exception)
- Mike Holt Enterprises — 2023 NEC changes: 210.8 GFCI
- Mike Holt Enterprises — 2023 NEC changes: 210.12 AFCI
- Mike Holt Enterprises — 2023 NEC: 210.52 receptacle outlets
- Mike Holt Enterprises — 2023 NEC change summaries
- ExpertCE — 2023 NEC receptacles near bathtubs and showers (406.9(C))
- ExpertCE — 2023 NEC ceiling fans in bathrooms (422.18)
- EC&M — The evolution of bathroom branch-circuit requirements
- EC&M — The apprentice’s guide to Article 410
Claims and figures are drawn from the sources above and provided for general guidance; your project may vary. For a fixed price on your specific bathroom, request a free estimate.